Notes:
8/20/2025 12:15:31 PM
FROM (E)POLE/(E)HH, BORE AND PLACE ±9988' OF (1)-2" CPC TO NEW HH/PEDS. PLACE (14) NEW HH (17"X30"X24"). PLACE (20) NEW BDGNP12. TCP NEEDED FOR ONE LANE FLAGGER, LANE SHIFT AND SHOULDER CLOSURE TO PERFORM ABOVE WORK.
10/28/2025 9:43:51 AM
Ryan Brady
TRAFFIC CONTROL 1ST SUBMITTAL
Due to the absence of a pedestrian detour plan for certain phases of work, it is understood that the pedestrian path of travel will remain unimpeded at all times, and that all existing accessibility features will remain unaffected. This understanding is based solely on the submitted Traffic Control Plans, as no verification of field conditions has been conducted. Should this understanding be incorrect, or should field conditions change, it remains the responsibility of the contractor to take corrective action and ensure compliance with the latest edition of the California Manual on Uniform Traffic Control Devices, as well as City of Modesto and ADA standards.
Pursuant to CA MUTCD Section 6D.02 Standard 03:
"Where pedestrians with visual disabilities normally use the closed sidewalk, a barrier that is detectable by a person with a visual disability traveling with the aid of a long cane shall be placed across the full width of the closed sidewalk."
For all sidewalk closures contractor shall install pedestrian barriers that are compliant with this standard. If providing a pedestrian detour, ensure pedestrians are only directed to cross at the nearest marked crosswalk and/or controlled intersection. If this is not a reasonable distance, provide pedestrians with directions for an alternative route.
Sheet 2 of 67: Install W1-4R for NB traffic on Erin Way.
Sheet 7 of 67: Remove W1-4Ls.
Sheet 8 of 67: Remove R4-8. If there is not enough room for two vehicle lanes at this intersection, convert to one lane flagging operation.
Sheet 10 of 67: Change W1-4R to W1-4L.
Sheet 26 of 67: Place the flaggers further in advance of the roundabout, so there is queuing space.
Sheet 28 of 67: Place the flaggers further in advance of the roundabout, so there is queuing space.
Sheet 33 of 67: Replace Eastbound W1-4R exiting the lane shift with W1-4L.
Sheet 34 of 67: Replace Eastbound W1-4L with W1-4R.
Sheet 35 of 67: Replace Eastbound W1-4Ls with W1-4Rs.
Sheet 38 of 67: Place the flaggers further in advance of the roundabout, so there is queuing space.
Sheet 41 of 67: Remove R4-8.
Sheet 61 of 67: Replace Eastbound W1-4Ls with W1-4Rs.